The low profile and flexible design of the Horizontal Basic (LH-B) fan coil is ideal for multiple applications. The slim, compact design is well suited for drop-ceiling, closet, hallway and other concealed applications. The LH-B comes with a powder-coated epoxy drain pan and a wide range of coil, motor and controls options. These models have no exterior cabinet.

The Horizontal Rear Return-Air Plenum (LH-R) is our basic fan coil with a galvanized rear-return air plenum. Ideal for mounting above ceilings, in closets, hallways and bathroom areas, the plenum conceals the unit’s blower motor, which is easily accessible for service by removing the bottom panel. Also available with Bottom Return Air Plenum (LH-Q)

The Horizontal Deluxe (LH-D) fan coil is designed for horizontal exposed ceiling-mounted applications. The LH-D is our basic unit housed in a cabinet intended for “free-blow” exposed ceiling mounting. This unit is ideal for remodel situations where adding AC ductwork is limited. Deluxe cabinets are constructed of cold-rolled steel and finished with a 385˙ baked-on tough, soft white epoxy powder-coated finish.


The Horizontal Flush Bottom Supply and Return (LH-E) is a recessed fan coil designed for flush ceiling applications. The telescoping frame and hinged access panel of the LH-E allows it to accommodate any type of ceiling. The LH-E comes in the same attractive and durable, powder-coated cabinet as the LH-D.

The Horizontal Flush (LH-F) is a recessed fan coil designed for flush ceiling applications. This unit is identical to the LH-E, yet designed to accommodate ducted supply air. The telescoping frame and hinged access panel of the LH-E allows it to accommodate any type of ceiling.

The Mini-Horizontal (MH) fan coil is an excellent choice for applications requiring 100% outside air for dehumidification, or areas requiring preheat/reheat. The MH is designed for smaller individual rooms in humid or extremely cold climates. Constructed of heavy-gauge, galvanized steel, the MH consists of a coil, washable filter and easily removable blower assembly.


Unit Type
Unit Size
Rated CFM
GPM
P.D. - FT.
H2O
Cooling Capacity
Total Cooling BTUH
Sensible Cooling BTUH
Power Input Watts
LH
002
240
1.1
1
5,300
4,800
98
LH
003
380
1.7
1.7
8,100
6,200
104
LH
004
430
2.4
1.5
11,000
8,700
134
LH
006
650
3.8
4.5
18,000
14,000
141
LH
008
910
5.0
4.9
24,600
18,100
215
LH
010
1,040
6.0
3.3
29,800
22,700
231
LH
012
1,150
6.2
5.2
36,000
27,000
249

Notes: Based on 80° DB and 67° WB EAT, 45° F EWT, 10° F temperature rise, high fan speed. Motor voltage 115/1/60 power source.
Air flow under dry coil conditions. Water pressure drops shown in feet of water. ** Data shown for two (2) motors.

Copyright 2008, williamscomfortprod.com All rights reserved.