The Vertical Basic (CV-B) is a high static, ducted vertical cased fan coil with bottom return. Primarily used in vertical floor-mounted or hideaway applications, the CV-B is furred into partition walls or hidden in closets, utility rooms and other concealed locations with a ducted discharge. A removable front access panel facilitates easy servicing. A one-inch discharge duct flange is standard on the top panel of each unit. Front Return Basic CV-K also available.
|
|
|
 |
|
The Vertical Deluxe (CV-D) is our CV-B Basic model primarily used in floor-mounted or exposed applications. The CV-D is finished in a soft white, powder coat epoxy and subjected to a 500 hour salt spray test in accordance with ASTM B117. Front Return Deluxe CV-J also available.
|
|
|
 |
|
The Vertical Front Return (CV-F) is a high static, ducted vertical fan coil for installation in a closet-type enclosure. The front panel is removable for easy service access to the slide-out blower assembly, with quick-connect plug. CV-F with return-air grille option allows unit to be furred-in. Grille mounts to drywall for easy access without the expense of a closet door. Vertical Front Return Deluxe CV-R also available.
|
|
|
|
|
 |
|
 |
|
Unit Type
|
|
Unit Size
|
|
Rated CFM
|
|
GPM
|
|
P.D. - FT.
H2O
|
|
Cooling Capacity
|
|
Total Cooling BTUH
|
|
Sensible Cooling BTUH
|
|
|
|
Power Input Watts
|
|
|
CV-F/R
|
|
06
|
|
730
|
|
3.8
|
|
1.0
|
|
20,700
|
|
16,900
|
|
260
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CV-F/R
|
|
08
|
|
960
|
|
5.5
|
|
2.1
|
|
29,400
|
|
23,000
|
|
360
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CV-F/R
|
|
10
|
|
1,060
|
|
6.2
|
|
3.0
|
|
34,000
|
|
26,400
|
|
383
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CV-F/R
|
|
12
|
|
1,300
|
|
7.4
|
|
4.8
|
|
43,000
|
|
32,800
|
|
540
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CV-F/R
|
|
15
|
|
1,580
|
|
10.6
|
|
6.0
|
|
56,000
|
|
41,000
|
|
533**
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CV-F/R
|
|
18
|
|
1,840
|
|
12.5
|
|
9.2
|
|
67,000
|
|
49,000
|
|
654**
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CV-F/R
|
|
22
|
|
2,010
|
|
14.0
|
|
12.4
|
|
75,000
|
|
54,300
|
|
768**
|
|
|
Notes: Based on 80° DB and 67° WB EAT, 45° F EWT, 10° F temperature rise, high fan speed. Motor voltage 115/1/60 power source.