The Vertical Basic (CV-B) is a high static, ducted vertical cased fan coil with bottom return. Primarily used in vertical floor-mounted or hideaway applications, the CV-B is furred into partition walls or hidden in closets, utility rooms and other concealed locations with a ducted discharge. A removable front access panel facilitates easy servicing. A one-inch discharge duct flange is standard on the top panel of each unit. Front Return Basic CV-K also available.

The Vertical Deluxe (CV-D) is our CV-B Basic model primarily used in floor-mounted or exposed applications. The CV-D is finished in a soft white, powder coat epoxy and subjected to a 500 hour salt spray test in accordance with ASTM B117. Front Return Deluxe CV-J also available.

The Vertical Front Return (CV-F) is a high static, ducted vertical fan coil for installation in a closet-type enclosure. The front panel is removable for easy service access to the slide-out blower assembly, with quick-connect plug. CV-F with return-air grille option allows unit to be furred-in. Grille mounts to drywall for easy access without the expense of a closet door. Vertical Front Return Deluxe CV-R also available.


Unit Type
Unit Size
Rated CFM
GPM
P.D. - FT.
H2O
Cooling Capacity
Total Cooling BTUH
Sensible Cooling BTUH
Power Input Watts
CV-F/R
06
730
3.8
1.0
20,700
16,900
260
CV-F/R
08
960
5.5
2.1
29,400
23,000
360
CV-F/R
10
1,060
6.2
3.0
34,000
26,400
383
CV-F/R
12
1,300
7.4
4.8
43,000
32,800
540
CV-F/R
15
1,580
10.6
6.0
56,000
41,000
533**
CV-F/R
18
1,840
12.5
9.2
67,000
49,000
654**
CV-F/R
22
2,010
14.0
12.4
75,000
54,300
768**

Notes: Based on 80° DB and 67° WB EAT, 45° F EWT, 10° F temperature rise, high fan speed. Motor voltage 115/1/60 power source.
Air flow under dry coil conditions. Water pressure drops shown in feet of water. ** Data shown for two (2) motors.